CASE STUDY / CONTROL ROOM

Make a tuning decision inspectable.

A controller that looks good on one nominal process can behave differently when delay, dynamics or measurement quality change.

CONTROL ROOMEXPERIMENT 04
A QUESTION WORTH TESTING

Faster.
But more resilient?

One process. Two controllers.
Make the trade-off visible.

DISTURBANCE0 s90 s180 s
Balanced AggressiveSynthetic model
THE MODELFOPDT + PID
Try the experiment
TRY ITPin a controller. Compare a preset.
INSPECT ITResponse · Saturation · Error

The question

How can an interactive experiment show the difference between a fast initial response and a controller that performs consistently across plausible process conditions?

My design decisions

Compare like with like
Use identical process variations and random seeds for both controllers. Otherwise an apparent improvement could come from an easier test.
Keep the interface responsive
Run repeated simulations in a Web Worker and discard outdated responses when inputs change. Keep a numerical table alongside the graphic.
Make the result portable
Encode the parameters, baseline and study settings in a versioned URL. A reviewer can reproduce a result without creating an account.

The model

The simulation uses a unity-gain first-order process with dead time, a bounded actuator and a PID controller with derivative-on-measurement. The baseline equations are tested against an analytic proportional-control solution. Numerical convergence is checked separately.

A paired comparison

Pin a controller, then change its tuning. Both designs run on the same process. In the robustness study, they also receive identical random process variations and measurement noise. A fixed seed makes the comparison repeatable.

GENERATED FROM THE MODEL / SEED 2026

Across 32 synthetic trials, the median absolute error is 10.38 for the balanced preset and 7.23 for the aggressive one.

Settings: ±20% variation in time constant and delay; measurement-noise standard deviation 0.01; 180 s runs. These are synthetic model results, not operating-plant measurements.

Results you can reproduce

One nominal run of the unvaried process, from the initial setpoint response through the load disturbance. Its absolute error is for this single 180-second run, so it differs slightly from the trial medians above.
MeasureBalancedAggressive
Startup overshoot0.0%4.2%
Rise time9.0 s4.9 s
Absolute error (this run)10.397.25

These values are computed from the model when the site builds. The faster response has to be weighed against overshoot, actuator limits and variation across the paired trials. There is no single score that substitutes for those decisions.

Why a Web Worker?

Repeated simulation should not block pointer, keyboard or input events. The main thread owns the controls and SVG. A separate worker returns versioned results; response IDs prevent an older request from overwriting a newer result.

What the evidence does not establish

The model omits actuator nonlinearities, coupled loops and plant safety constraints. Trial percentiles describe the chosen synthetic conditions. They do not establish confidence bounds or safe tuning for real equipment.

Reproduce the experiment →
Terms used on this page
PID controller
The most common feedback controller: it adjusts an output using the present error, its accumulated history and how fast it is changing.
Dead time
The delay between a control action and the first sign of its effect on the measured process.
All terms →